105
2 Parameters
2.2 List of parameters
Description: Sets the brake holding torque.
Description: Sets the brake moment of inertia.
Description: Setting to inhibit the calculation of reference parameters (e.g. p2000) when automatically calculating the motor and
closed-loop control parameters (p0340, p3900).
Value: 0: No
1: Yes
Notice: The inhibit for the reference value calculation is canceled when new motor parameters (e.g. p0305) are entered and
only one drive data set exists (p0180 = 1). This is the case during initial commissioning.
Once the motor and control parameters have been calculated (p0340, p3900), the inhibit for the reference value
calculation is automatically re-activated.
Note: If value = 0:
The automatic calculation (p0340, p3900) overwrites the reference parameters.
If value = 1:
The automatic calculation (p0340, p3900) does not overwrite the reference parameters.
Description: Sets the input terminal for the measuring probe for speed actual value measurement.
Value: 0: No meas probe
21: DI 1 (X07.2)
23: DI 3 (X08.2)
Dependency: Refer to: p0581
Refer to: A07498
Note: DI: Digital Input
p0553[0...n] Brake holding torque / Brake M_hold
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: MDS
Unit group: 7_1 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
0 [Nm] 340.28235E36 [Nm] 0 [Nm]
p0554[0...n] Brake moment of inertia / Brake J
Access level: 3 Calculated: - Data type: Integer32
Can be changed: T Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 [kgm²] 2147483647 [kgm²] 0 [kgm²]
p0573 Inhibit automatic reference value calculation / Inhibit calc
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
p0580 Measuring probe input terminal / MT input terminal
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 23 0