2 Parameters
2.2 List of parameters
SINAMICS G120D
344 List Manual (LH14), 01/2016, A5E33842313
Dependency: Refer to: p2543, p2544, r2684
Refer to: F07451
Note: The following applies for the setting of the standstill and positioning monitoring time:
Standstill monitoring time (p2543) <= positioning monitoring time (p2545)
Description: Sets the tolerance for the dynamic following error monitoring.
If the dynamic following error (r2563) exceeds the selected tolerance, then an appropriate fault is output.
Value = 0 --> The dynamic following error monitoring is de-activated.
Dependency: Refer to: r2563, r2684
Refer to: F07452
Note: The tolerance bandwidth is intended to prevent the dynamic following error monitoring incorrectly responding due to
operational control sequences (e.g. during load surges).
Description: Sets the cam switching position 1.
Dependency: Refer to: p2548, r2683
Caution: Only after the axis has been referenced can it be guaranteed that the cam switching signals when output have a
"true" position reference.
Note: Position actual value <= cam switching position 1 --> r2683.8 = 1 signal
Position actual value > cam switching position 1 --> r2683.8 = 0 signal
Description: Sets the cam switching position 2.
Dependency: Refer to: p2547, r2683
Caution: Only after the axis has been referenced can it be guaranteed that the cam switching signals when output have a
"true" position reference.
Note: Position actual value <= cam switching position 2 --> r2683.9 = 1 signal
Position actual value > cam switching position 2 --> r2683.9 = 0 signal
Description: Sets the signal source for the position controller enable 1.
Dependency: Refer to: r0899, p2550
p2546[0...n] LR dynamic following error monitoring tolerance / s_delta_monit tol
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 1 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 4025
Min Max Factory setting
0 [LU] 2147483647 [LU] 1000 [LU]
p2547 LR cam switching position 1 / Cam position 1
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 1 Calculated: - Data type: Integer32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 4025
Min Max Factory setting
-2147483648 [LU] 2147483647 [LU] 0 [LU]
p2548 LR cam switching position 2 / Cam position 2
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 1 Calculated: - Data type: Integer32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 4025
Min Max Factory setting
-2147483648 [LU] 2147483647 [LU] 0 [LU]
p2549 BI: LR enable 1 / Enable 1
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 1 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 4015
Min Max Factory setting
- - 899.2