2 Parameters
2.2 List of parameters
SINAMICS G120D
434 List Manual (LH14), 01/2016, A5E33842313
Dependency: Refer to: p8980
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Selects the storage medium for access via the USB mass storage.
Value: 1: Memory card
2: Flash r/w internal
Note: A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Setting the USB functionality.
Value: 1: USS commissioning via the virtual COM port
2: Only memory access
3: USB commissioning and memory access
Note: COMM: Commissioning.
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Sets the enable signals for the safe motion monitoring.
Dependency: Refer to: p9501
Refer to: F01682, F01683
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: For bit 30 = 1, PROFIsafe telegram 900 must be configured in the F host.
A change only becomes effective after a POWER ON.
F-DI: Failsafe Digital Input
SDI: Safe Direction (safe motion direction)
SLS: Safely Limited Speed
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
p8991 USB memory access / USB mem acc
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 2 1
p8999 USB functionality / USB Fct
Access level: 4 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 3 3
p9301 SI Motion enable safety functions (processor 2) / SI Mtn enable P2
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 0000 0000 0000 0000 0000
0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Enable SI Motion Enable Inhibit -
16 Enable SSM hysteresis and filtering Enable Inhibit 2823
17 Enable SDI Enable Inhibit 2824
30 Enable F-DI in PROFIsafe telegram 900 Enable Inhibit -