Siemens SINAMICS G120D CU240D-2 DP - p2247[0...n] Technology controller motorized potentiometer ramp-up time; Tec_ctr mop t_r­up; p2248[0...n] Technology controller motorized potentiometer ramp-down time; Tec_ctrMop t_rdown; r2250 CO: Technology controller motorized potentiometer setpoint after RFG; Tec_ctr mop aftRFG; p2251 Technology controller mode; Tec_ctrl mode

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G120D
320 List Manual (LH14), 01/2016, A5E33842313
Description: Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency: Refer to: p2248
Note: The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-up is correspondingly extended.
Description: Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency: Refer to: p2247
Note: The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-down is correspondingly extended.
Description: Displays the effective setpoint after the internal ramp-function generator for the motorized potentiometer of the
technology controller.
Dependency: Refer to: r2245
Description: Sets the mode for using the technology controller output.
Value: 0: Technology controller as main speed setpoint
1: Technology controller as supplementary speed setpoint
Dependency: p2251 = 0, 1 is only effective if the enable signal of the technology controller is interconnected (p2200 > 0).
p2247[0...n] Technology controller motorized potentiometer ramp-up time / Tec_ctr mop t_r-up
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 7954
Min Max Factory setting
0.0 [s] 1000.0 [s] 10.0 [s]
p2248[0...n] Technology controller motorized potentiometer ramp-down time /
Tec_ctrMop t_rdown
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 7954
Min Max Factory setting
0.0 [s] 1000.0 [s] 10.0 [s]
r2250 CO: Technology controller motorized potentiometer setpoint after RFG /
Tec_ctr mop aftRFG
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: 9_1 Unit selection: p0595 Func. diagram: 7954
Min Max Factory setting
- [%] - [%] - [%]
p2251 Technology controller mode / Tec_ctrl mode
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0 1 0