EasyManua.ls Logo

Siemens SINAMICS G120D CU240D-2 DP - r2672 CO: EPOS actual velocity setpoint; v_set act; r2673 CO: EPOS actual acceleration override; a_over act; r2674 CO: EPOS actual deceleration override; ­a_over act; r2675 CO: EPOS actual task; Task act

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
377
2 Parameters
2.2 List of parameters
Description: Displays the velocity setpoint presently being processed.
Description: Displays the acceleration override presently being processed.
Note: An override of 100% is effective in the "jogging" and "search for reference" operating modes.
Description: Displays the deceleration override presently being processed.
Note: An override of 100% is effective in the "jogging" and "search for reference" operating modes.
Description: Displays the task that is presently being processed.
Value: 0: Inactive
1: POSITIONING
2: FIXED STOP
3: ENDLESS_POS
4: ENDLESS_NEG
5: WAITING
6: GOTO
7: SET_O
8: RESET_O
9: JERK
Dependency: Refer to: p2621
r2672 CO: EPOS actual velocity setpoint / v_set act
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 1 Calculated: - Data type: Integer32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 3610, 3612, 3616,
3620
Min Max Factory setting
- [1000 LU/min] - [1000 LU/min] - [1000 LU/min]
r2673 CO: EPOS actual acceleration override / a_over act
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 3610, 3612, 3616,
3620
Min Max Factory setting
- [%] - [%] - [%]
r2674 CO: EPOS actual deceleration override / -a_over act
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 3610, 3612, 3616,
3620
Min Max Factory setting
- [%] - [%] - [%]
r2675 CO: EPOS actual task / Task act
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 1 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 3616
Min Max Factory setting
0 9 -