SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313 
127
2 Parameters
2.2 List of parameters
Dependency: The setpoint for the input signals is specified using p0796.
Refer to: p0796
Note: This parameter is not saved when data is backed up (p0971).
AI: Analog Input
DI: Digital Input
Description: Sets the simulation mode for digital inputs.
Dependency: The setpoint for the input signals is specified using p0796.
Refer to: p0796
Note: This parameter is not saved when data is backed up (p0971).
DI: Digital Input
Description: Sets the setpoint for the input signals in the digital input simulation mode.
Dependency: The simulation of a digital input is selected using p0795.
Refer to: p0795
Note: This parameter is not saved when data is backed up (p0971).
AI: Analog Input
DI: Digital Input
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI0 (X07.1) Simulation Terminal eval -
01 DI1 (X07.2) Simulation Terminal eval -
02 DI2 (X08.1) Simulation Terminal eval -
03 DI3 (X08.2) Simulation Terminal eval -
04 DI4 (X09.1) Simulation Terminal eval -
05 DI5 (X09.2) Simulation Terminal eval -
11 DI11 (X10.3, 7) AI0 Simulation Terminal eval -
12 DI12 (X10.4, 7) AI1 Simulation Terminal eval -
p0795 CU digital inputs simulation mode / CU DI simulation
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2201, 2210, 2256
Min Max Factory setting 
-  -  0000 0000 bin 
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI0 (X07.1) Simulation Terminal eval -
01 DI1 (X07.2) Simulation Terminal eval -
02 DI2 (X08.1) Simulation Terminal eval -
03 DI3 (X08.2) Simulation Terminal eval -
04 DI4 (X09.1) Simulation Terminal eval -
05 DI5 (X09.2) Simulation Terminal eval -
p0796 CU digital inputs simulation mode setpoint / CU DI simul setp
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2201, 2210, 2256
Min Max Factory setting 
-  -  0000 0000 0000 0000 bin 
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X07.4) High Low -
01 DI 1 (X07.2) High Low -
02 DI 2 (X08.4) High Low -
03 DI 3 (X08.2) High Low -
04 DI 4 (X09.4) High Low -
05 DI 5 (X09.2) High Low -
11 DI 11 (X10.3) AI 0 High Low -
12 DI 12 (X10.4) AI 1 High Low -