SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
467
2 Parameters
2.2 List of parameters
Index: [0] = Setpoint limiting positive
[1] = Setpoint limiting negative
[2] = Setpoint limit absolute
Dependency: For SLS: r9733[0] = p9531[x] x p9533 (converted from the load side to the motor side)
For SDI negative: r9733[0] = 0
For SLS: r9733[1] = - p9531[x] x p9533 (converted from the load side to the motor side)
For SDI positive: r9733[1] = 0
[x] = Selected SLS stage
Conversion factor from the motor side to the load side:
- motor type = rotary and axis type = linear: p9522 / (p9521 x p9520)
- otherwise: p9522 / p9521
Refer to: p9531, p9533
Notice: If p1051 = r9733[0] is interconnected, p1052 = r9733[1] must also be interconnected and vice versa.
If only the absolute value of the setpoint velocity limiting is required, r9733[2] must be interconnected.
Note: If the "SLS" function is not selected, r9733[0] shows p1082 and r9733[1] shows -p1082.
The display in r9733 can be delayed by up to one Safety monitoring clock cycle as compared to the display in r9720
and r9722.
Description: Display and BICO output for status word S_ZSW1B of the safety information channel.
Notice: For bit 07:
An internal event is displayed if a STOP A ... F is active.
The signal state behaves in an opposite way to the PROFIsafe Standard.
Note: This parameter is only supplied with actual values if SI Motion functions are active. For Safety Integrated Basic
Functions the value is equal to zero.
Description: Status signal for safety-relevant motion monitoring functions integrated in the drive.
r9734.0...14 CO/BO: SI Safety Info Channel status word S_ZSW1B / SIC S_ZSW1B
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 STO active Yes No -
01 SS1 active Yes No -
04 SLS active Yes No -
06 SLS selected Yes No -
07 Internal event Yes No -
09 Select SLS bit0 Yes No -
10 Select SLS bit1 Yes No -
12 SDI positive selected Yes No -
13 SDI neg selected Yes No -
14 ESR retract requested Yes No -
r9742.0...15 CO/BO: SI Motion drive-integrated status signals (processor 2) / SI Mtn int stat P2
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level: 4 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2840, 2855
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 STO or safe pulse suppression active Yes No -
01 SS1 active Yes No -
04 SLS active Yes No -
07 Internal event No Yes -
09 Active SLS stage bit 0 Set Not set -
10 Active SLS stage bit 1 Set Not set -
15 SSM (speed below limit value) Yes No 2823