EasyManua.ls Logo

Siemens SINAMICS G120D CU240D-2 DP - Fig. 3-156 7264 - INT 0, DIF 0

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
769
3 Function diagrams
3.17 Free function blocks
Fig. 3-156 7264 – INT 0, DIF 0
- 7264 -
Function diagram
87654321
fp_7264_97_61.vsd
Free function blocks - Control function blocks
G120D CU240D-2
09.12.2015 V4.7.6
INT 0, DIF 0
INT 0
TI
S
d
dt
TD
DIF 0
Integrating algorithm: Y(n) = Y(n-1) + (T_sample / Ti) * X(n)
Differentiating algorithm: Y(n) = (X(n) - X(n-1)) * (TD / T_sample)
r20261
INT 0 output Y
INT 0 QL
r20263
INT 0 RTG
5 ... 9999
p20264 (9999)
INT 0 RunSeq
0 ... 32000
p20265 (700)
INT 0 upper lim LU
-340.28235E36 ... 340.28235E36
p20257 (0.0000)
INT 0 lower lim LL
-340.28235E36 ... 340.28235E36
p20258 (0.0000)
INT 0 QU
r20262
INT 0 inputs
[0]
p20256
[1]
(0)
INT 0 acc set val
p20260
Input
Set value
INT 0 T_Integr ms
0.00 ... 340.28235E36
p20259 (0.00)
DIF 0 T_diff ms
0.00 ... 340.28235E36
p20285 (0.00)
DIF 0 RunSeq
0 ... 32000
p20288 (750)
DIF 0 RTG
5 ... 9999
p20287 (9999)
DIF 0 input X
(0)
p20284
r20286
DIF 0 output Y
X
SV
LU
LL
QU
Y
QL
YX
INT (integrator)
DIF (derivative-action element)

Table of Contents