EasyManua.ls Logo

Siemens SINAMICS G120D CU240D-2 DP - p1575[0...n] Voltage target value limit; U_tgt val lim; p1580[0...n] Efficiency optimization; Efficiency opt.; p1582[0...n] Flux setpoint smoothing time; Flux setp T_smth; r1583 Flux setpoint smoothed; Flux setp smooth

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G120D
230 List Manual (LH14), 01/2016, A5E33842313
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0500
Note: In the field weakening range, it must be expected that the control dynamic performance is somewhat restricted due to
the limited possibilities of controlling/adjusting the voltage. This can be improved by increasing the voltage reserve.
Increasing the reserve reduces the steady-state maximum output voltage (r0071).
Description: Sets the limit of the voltage target value.
In steady-state field weakening operation this corresponds to the required output voltage.
The value of 100% refers to p0304.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note: The output voltage is only limited if the maximum output voltage (r0071) minus the voltage reserve (p1574)
corresponds to a value higher than p1575.
Limiting via p1575 allows the influence of the voltage ripple of the line supply voltage to be eliminated at the operating
point.
Description: Sets the efficiency optimization.
When optimizing the efficiency, the flux setpoint of the closed-loop control is adapted as a function of the load.
For p1580 = 100 %, under no-load operating conditions, the flux setpoint is reduced to 50 % of the rated motor flux.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note: It only makes sense to activate this function if the dynamic response requirements of the speed controller are low.
In order to avoid oscillations, if required, the speed controller parameters should be adapted (increase Tn, reduce
Kp).
Further, the smoothing time of the flux setpoint filter (p1582) should be increased.
Description: Sets the smoothing time for the flux setpoint.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description: Displays the smoothed flux setpoint.
The value is referred to the rated motor flux.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
p1575[0...n] Voltage target value limit / U_tgt val lim
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6725
Min Max Factory setting
50.00 [%] 300.00 [%] 200.00 [%]
p1580[0...n] Efficiency optimization / Efficiency opt.
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6722
Min Max Factory setting
0 [%] 100 [%] 0 [%]
p1582[0...n] Flux setpoint smoothing time / Flux setp T_smth
Access level: 3 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6722, 6724
Min Max Factory setting
4 [ms] 5000 [ms] 15 [ms]
r1583 Flux setpoint smoothed / Flux setp smooth
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6722, 6723, 6724
Min Max Factory setting
- [%] - [%] - [%]

Table of Contents

Related product manuals