SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
129
2 Parameters
2.2 List of parameters
Description: Sets the number for data transfer of a parameter backup from/to memory card.
Transfer from memory card to device memory (p0804 = 1):
- sets the source of parameter backup (e.g. p0802 = 48 --> PS048xxx.ACX is the source).
Transfer from non-volatile device memory to memory card (p0804 = 2):
- sets the target of parameter backup (e.g. p0802 = 23 --> PS023xxx.ACX is the target).
Dependency: Refer to: p0803, p0804
Note: The volatile device memory is not influenced by data transfer.
Description: Sets the number for data transfer of a parameter backup from/to the non-volatile device memory.
Transfer from memory card to device memory (p0804 = 1):
- sets the target of the parameter backup (e.g. p0803 = 10 --> PS010xxx.ACX is the target).
Transfer from non-volatile device memory to memory card (p0804 = 2):
- sets the source of the parameter backup (e.g. p0803 = 11 --> PS011xxx.ACX is the source).
Value: 0: Source/target standard
10: Source/target with setting 10
11: Source/target with setting 11
12: Source/target with setting 12
30: Source/target with setting 30
Dependency: Refer to: p0802, p0804
Note: The volatile device memory is not influenced by data transfer.
Description: Sets the transfer direction and start of data transfer between the memory card and non-volatile device memory.
Example 1:
The parameter backup is to be transferred from the non-volatile device memory to the memory card with setting 0.
The parameter backup is to be stored on the memory card with setting 22.
p0802 = 22 (parameter backup stored on memory card as target with setting 22)
p0803 = 0 (parameter backup stored in device memory as source with setting 0)
p0804 = 2 (start data transfer from device memory to memory card)
--> PS000xxx.ACX is transferred from device memory to memory card and stored as PS022xxx.ACX.
--> the parameter backup PS022xxx.ACX on the memory card can be used for data backup.
p0802 Data transfer: memory card as source/target / mem_card src/targ
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 100 0
p0803 Data transfer: device memory as source/target / Dev_mem src/targ
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 30 0
p0804 Data transfer start / Data transf start
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1100 0