Siemens SINAMICS G120D CU240D-2 DP - p1123[0...n] Ramp-function generator minimum ramp-up time; RFG t_RU min; p1127[0...n] Ramp-function generator minimum ramp-down time; RFG t_RD min; p1130[0...n] Ramp-function generator initial rounding-off time; RFG t_start_round; p1131[0...n] Ramp-function generator final rounding-off time; RFG t_end_delay

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
175
2 Parameters
2.2 List of parameters
Description: Sets the minimum ramp-up time.
The ramp-up time (p1120) is limited internally to this minimum value.
Dependency: Refer to: p1082
Note: The setting should be based on the startup times (r0345) of the motor.
If the maximum speed p1082 changes, p1123 is re-calculated.
Description: Sets the minimum ramp-down time.
The ramp-down time (p1121) is limited internally to this minimum value.
The parameter cannot be set shorter than the minimum ramp-up time (p1123).
Dependency: Refer to: p1082
Note: For U/f control and sensorless vector control (see p1300), a ramp-down time of 0 s does not make sense. The setting
should be based on the startup times (r0345) of the motor.
If the maximum speed p1082 changes, p1127 is re-calculated.
Description: Sets the initial rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description: Sets the final rounding-off time for the extended ramp generator.
The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
p1123[0...n] Ramp-function generator minimum ramp-up time / RFG t_RU min
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [s] 999999.000 [s] 0.000 [s]
p1127[0...n] Ramp-function generator minimum ramp-down time / RFG t_RD min
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [s] 999999.000 [s] 0.000 [s]
p1130[0...n] Ramp-function generator initial rounding-off time / RFG t_start_round
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1131[0...n] Ramp-function generator final rounding-off time / RFG t_end_delay
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]