SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
35
2 Parameters
2.2 List of parameters
Dependency: Refer to: p0043
Note: The signal can be displayed as process variable (scaling: 1 = 1 Wh).
This is enabled in p0043.
The display is also reset with p0040 = 1.
If an enable is present in r0043 when the Control Unit powers up, then the value from r0039 is transferred into r0042.
As r0039 serves as a reference signal for r0042, due to format reasons, the process energy display can only process
values of r0039 up to 2147483 kWh. r0039 should also be reset using this value.
Description: Sets the signal source to enable/reset the process energy display in r0042.
BI: p0043 = 1 signal:
The process energy display is enabled in r0042.
Dependency: Refer to: r0042
Description: Sets the smoothing time constant for the following display values:
r0063[1], r0068[1], r0080[1], r0082[1].
Description: Display and BICO output for missing enable signals that are preventing the closed-loop drive control from being
commissioned.
p0043 BI: Enable energy usage display / Enab energy usage
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0
p0045 Display values smoothing time constant / Disp_val T_smooth
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 6714, 8012
Min Max Factory setting
0.00 [ms] 10000.00 [ms] 4.00 [ms]
r0046.0...31 CO/BO: Missing enable sig / Missing enable sig
Access level: 1 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2634
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 OFF1 enable missing Yes No 7954
01 OFF2 enable missing Yes No -
02 OFF3 enable missing Yes No -
03 Operation enable missing Yes No -
04 DC braking enable missing Yes No -
08 Safety enable missing Yes No -
10 Ramp-function generator enable missing Yes No -
11 Ramp-function generator start missing Yes No -
12 Setpoint enable missing Yes No -
16 OFF1 enable internal missing Yes No -
17 OFF2 enable internal missing Yes No -
18 OFF3 enable internal missing Yes No -
19 Pulse enable internal missing Yes No -
20 DC braking internal enable missing Yes No -
21 Power unit enable missing Yes No -
26 Drive inactive or not operational Yes No -
27 De-magnetizing not completed Yes No -
28 Brake open missing Yes No -
30 Speed controller inhibited Yes No -
31 Jog setpoint active Yes No -