2 Parameters
2.2 List of parameters
Description: Displays the time between the last two BERO pulses.
The measuring time is specified as 32-bit value with a resolution of 1/48 µs.
If a new pulse is not received before the maximum measured time in p0583 expires, then r0587 is set to the
maximum measuring time.
Dependency: Refer to: p0580
Note: For p0580 = 0 (no measuring probe), a value of zero is displayed here.
Description: Displays the number of measuring pulses that have occurred (been received) up until now.
Dependency: Refer to: p0580
Note: After reaching 4294967295 (2^32 - 1), the counter starts again at 0.
Description: Displays the time since the last measuring pulse was detected.
The delay time is specified as 32-bit value with a resolution of 1/48 µs.
When a measuring pulse occurs (is received) the delay time is reset and is limited to the maximum measuring time in
p0583.
Dependency: Refer to: p0580
Note: For p0580 = 0 (no measuring probe), a value of zero is displayed here.
Description: Selects the units for the parameters of the technology controller.
For p0595 = 1, 2, the reference quantity set in p0596 is not active.
Value: 1: %
2: 1 referred no dimensions
3: bar
4: °C
5: Pa
6: ltr/s
7: m³/s
8: ltr/min
9: m³/min
10: ltr/h
r0587 CO: Measuring probe measuring time measured / MT t_meas measured
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
r0588 CO: Measuring probe pulse counter / MT pulse counter
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
r0589 Measuring probe delay time / MT t_delay
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p0595 Technological unit selection / Tech unit select
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(5) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 47 1