Siemens SINAMICS G120D CU240D-2 DP - p1702[0...n] Isd current controller pre-control scaling; Isd_ctr_prectrScal; p1703[0...n] Isq current controller pre-control scaling; Isq_ctr_prectrScal; p1715[0...n] Current controller P gain; I_ctrl Kp; p1717[0...n] Current controller integral-action time; I_ctrl Tn

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
235
2 Parameters
2.2 List of parameters
Description: Sets the scaling of the dynamic current controller pre-control for the flux-generating current component Isd.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Note: The parameter is effective for permanent-magnet synchronous motors.
Description: Sets the scaling of the dynamic current controller pre-control for the torque/force-generating current component Isq.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description: Sets the proportional gain of the current controller.
This value is automatically pre-set using p3900 or p0340 when commissioning has been completed.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description: Sets the integral-action time of the current controller.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1715
Description: Displays the actual output of the Isq current controller (torque/force generating current, PI controller).
The value contains the proportional and integral components of the PI controller.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
p1702[0...n] Isd current controller pre-control scaling / Isd_ctr_prectrScal
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6714
Min Max Factory setting
0.0 [%] 200.0 [%] 70.0 [%]
p1703[0...n] Isq current controller pre-control scaling / Isq_ctr_prectrScal
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6714
Min Max Factory setting
0.0 [%] 200.0 [%] 60.0 [%]
p1715[0...n] Current controller P gain / I_ctrl Kp
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6714
Min Max Factory setting
0.000 100000.000 0.000
p1717[0...n] Current controller integral-action time / I_ctrl Tn
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 5714, 6700, 6714,
7017
Min Max Factory setting
0.00 [ms] 1000.00 [ms] 2.00 [ms]
r1718 CO: Isq controller output / Isq_ctrl outp
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Unit group: 5_1 Unit selection: p0505 Func. diagram: 6714
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]