SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
79
2 Parameters
2.2 List of parameters
Notice: This parameter is automatically pre-set for encoders from the encoder list (p0400).
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note: ZM: Zero mark
For bit 12 (equidistant zero mark):
The zero marks occur at regular intervals (e.g. rotary encoder with 1 zero mark per revolution or linear encoder with
constant zero mark distance).
The bit activates monitoring of the zero mark distance (p0424/p0425, linear/rotary) or in the case of the linear
encoder with 1 zero mark and p0424 = 0 zero mark monitoring is activated.
For bit 13 (irregular zero mark):
The zero marks occur at irregular intervals (e.g. a linear scale with only 1 zero mark in the traversing range). The zero
mark distance is not monitored.
For bit 14 (distance-coded zero mark):
The distance (clearance) between two or several consecutive zero marks allows the absolute position to be
calculated.
Description: Settings for the track A/B in a square-wave encoder.
For square-wave encoders, p0404.3 must also be 1.
Notice: This parameter is automatically pre-set for encoders from the encoder list (p0400).
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note: For bit 00:
For G120D, only "Bipolar" is supported.
For bit 01:
For G120D, only "HTL" is supported.
For bit 02:
When the function is activated, track monitoring can be de-activated by setting p0437.26.
For bit 03:
For G120D, only "Same as track A/B" is supported.
For bit 04:
For G120D, only "Low" is supported.
Description: Sets the grid division for a linear encoder.
Notice: This parameter is automatically pre-set for encoders from the encoder list (p0400).
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note: The lowest permissible value is 250 nm.
p0405[0...n] Square-wave encoder track A/B / Sq-wave enc A/B
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(4) Scaling: - Dyn. index: EDS, p0140
Unit group: - Unit selection: - Func. diagram: 4704
Min Max Factory setting
- - 0000 1001 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Signal Bipolar Unipolar -
01 Level TTL HTL -
02 Track monitoring A/B <> -A/B None -
03 Zero pulse Same as A/B track 24 V unipolar -
04 Switching threshold High Low -
p0407[0...n] Linear encoder grid division / Enc grid div
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(4) Scaling: - Dyn. index: EDS
Unit group: - Unit selection: - Func. diagram: 4010, 4704
Min Max Factory setting
0 [nm] 250000000 [nm] 16000 [nm]