EasyManua.ls Logo

Siemens SINAMICS G120D CU240D-2 DP - r0047 Motor data identification and speed controller optimization; MotID and n_opt; r0050.0...1 CO;BO: Command Data Set CDS effective; CDS effective; r0051.0...1 CO;BO: Drive Data Set DDS effective; DDS effective

Siemens SINAMICS G120D CU240D-2 DP
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
37
2 Parameters
2.2 List of parameters
Description: Displays the actual status for the motor data identification (stationary measurement) and the speed controller
optimization (rotating measurement).
Value: 0: No measurement
115: Measurement q leakage inductance (part 2)
120: Speed controller optimization (vibration test)
140: Calculate speed controller setting
150: Measurement moment of inertia
170: Measurement magnetizing current and saturation characteristic
195: Measurement q leakage inductance (part 1)
200: Rotating measurement selected
220: identification leakage inductance
230: Identification rotor time constant
240: Identification stator inductance
250: Identification stator inductance LQLD
260: Identification circuit
270: Identification stator resistance
290: Identification valve lockout time
300: Stationary measurement selected
Description: Displays the effective Command Data Set (CDS).
Dependency: Refer to: p0810, p0811, r0836
Note: The Command Data Set selected using a binector input (e.g. p0810) is displayed using r0836.
Description: Displays the effective Drive Data Set (DDS).
Dependency: Refer to: p0820, p0821, r0837
Note: When selecting the motor data identification routine and the rotating measurement, the drive data set changeover is
suppressed.
r0047 Motor data identification and speed controller optimization / MotID and n_opt
Access level: 1 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 300 -
r0050.0...1 CO/BO: Command Data Set CDS effective / CDS effective
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8560
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 CDS eff bit 0 ON OFF -
01 CDS eff bit 1 ON OFF -
r0051.0...1 CO/BO: Drive Data Set DDS effective / DDS effective
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8565
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DDS eff bit 0 ON OFF -
01 DDS eff bit 1 ON OFF -

Table of Contents

Related product manuals