2 Parameters
2.2 List of parameters
SINAMICS G120D
478 List Manual (LH14), 01/2016, A5E33842313
Dependency: Refer to: r9772
Note: For bit 00:
When STO is selected, the cause is displayed in bits 16 ... 21.
For bit 18:
When the bit is set, STO is selected via PROFIsafe.
Description: Displays the Safety Integrated status on processor 2.
Dependency: Refer to: r9772
Note: For bit 00:
When STO is selected, the cause is displayed in bits 16 ... 21.
For bit 18:
When the bit is set, STO is selected via PROFIsafe.
Description: Displays the checksum for the Safety Integrated parameters checked using checksums on processor 2 (actual
checksum).
Dependency: Refer to: r9798, p9899
07 STO terminal state on processor 2 (Basic
Functions)
High Low -
09 STOP A cannot be acknowledged active Yes No 2802
10 STOP A active Yes No 2802
15 STOP F active Yes No 2802
16 STO cause: Safety comm. mode Yes No -
17 STO cause selection via terminal (Basic
Functions)
Yes No -
18 STO cause: Selection via motion monitoring
functions
Yes No -
20 STO cause selection PROFIsafe (Basic
Functions)
Yes No -
21 STO cause selection on the other
monitoring channel
Yes No -
r9872.0...21 CO/BO: SI status (processor 2) / SI Status P2
CU240D-2_DP
CU240D-2_PN
Access level: 2 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2804
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 STO selected on processor 2 Yes No 2810
01 STO active on processor 2 Yes No 2810
07 STO terminal state on processor 2 (Basic
Functions)
High Low -
09 STOP A cannot be acknowledged active Yes No 2802
10 STOP A active Yes No 2802
15 STOP F active Yes No 2802
16 STO cause: Safety comm. mode Yes No -
17 STO cause selection via terminal (Basic
Functions)
Yes No -
20 STO cause selection PROFIsafe (Basic
Functions)
Yes No -
21 STO cause selection on the other
monitoring channel
Yes No -
r9898 SI actual checksum SI parameters (processor 2) / SI act_chksm P2
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2800
Min Max Factory setting
- - -