Description: Display and BICO output for the control word of the setpoint channel.
Description: Displays the status word for the ramp-function generator (RFG).
Note: For bit 02:
The bit is the result of the OR logic operation - bit 00 and bit 01.
Description: Sets the operating mode for flying restart.
The flying restart allows the drive converter to be switched on while the motor is still rotating. In so doing, the drive
converter output frequency is changed until the actual motor speed/velocity is found. The motor then accelerates up
to the setpoint at the ramp-function generator setting.
Value: 0: Flying restart inactive
1: Flying restart always active (start in setpoint direction)
4: Flying restart always active (start only in setpoint direction)
r1198.0...15 CO/BO: Control word setpoint channel / STW setpoint chan
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2505
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fixed setp bit 0 Yes No 3010
01 Fixed setp bit 1 Yes No 3010
02 Fixed setp bit 2 Yes No 3010
03 Fixed setp bit 3 Yes No 3010
05 Inhibit negative direction Yes No 3040
06 Inhibit positive direction Yes No 3040
11 Setpoint inversion Yes No 3040
13 Motorized potentiometer raise Yes No 3020
14 Motorized potentiometer lower Yes No 3020
15 Bypass ramp-function generator Yes No 3060,
3070
r1199.0...8 CO/BO: Ramp-function generator status word / RFG ZSW
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 3001, 3080
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Ramp-up active Yes No -
01 Ramp-down active Yes No -
02 RFG active Yes No -
03 Ramp-function generator set Yes No -
04 Ramp-function generator held Yes No -
05 Ramp-function generator tracking active Yes No -
06 Maximum limit active Yes No -
07 Ramp-function generator acceleration
positive
Yes No -
08 Ramp-function generator acceleration
negative
Yes No -
p1200[0...n] Flying restart operating mode / FlyRest op_mode
Access level: 2 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6300
Min Max Factory setting
0 4 0