SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313 
401
2 Parameters
2.2 List of parameters
Note: The individual bits are only set if the appropriate action has been initiated and successfully completed.
When motor rating plate parameters are changed, the final display is reset.
Description: Displays the base voltage for the alternating voltage in the context of motor data identification.
0:
No alternating voltages. The function is de-activated.
<0:
Automatic determination of the base voltage and wobbulation / self-setting based on the converter and the connected 
motor.
Otherwise:
Base voltage for alternating current generation in volts (wobbulation active).
Description: Successfully completed component of the last motor data identification carried out.
Dependency: Refer to: r3925
Note: The parameter is a copy of p1909.
12 Automatic parameterization as dynamic 
drive control
Yes No -
15 Motor equivalent circuit diagram parameters 
changed
Yes No -
r3926[0...n] Voltage generation alternating base voltage amplitude / U_gen altern base
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: MDS
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting 
- [V] - [V] - [V]
r3927[0...n] Motor data identification control word / MotID STW
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting 
- - - 
Bit field: Bit Signal name 1 signal 0 signal FP
00 Stator inductance estimate no 
measurement
Yes No -
02 Rotor time constant estimate no 
measurement
Yes No -
03 Leakage inductance estimate no 
measurement
Yes No -
05 Determine Tr and Lsig evaluation in the time 
range
Yes No -
06 Activate vibration damping Yes No -
07 De-activate vibration detection Yes No -
11 De-activate pulse measurement Lq Ld Yes No -
12 De-activate rotor resistance Rr 
measurement
Yes No -
14 De-activate valve interlocking time 
measurement
Yes No -
15 Determine only stator resistance, valve 
voltage fault, dead time
Yes No -
16 Short motor identification (lower quality) Yes No -
17 Measurement without control parameter 
calculation
Yes No -
18 After motID direct transition into operation Yes No -
19 After MotID automatically save results Yes No -
20 Estimate cable resistance Yes No -
21 Calibrating the output voltage measurement Yes No -
22 Only identify circle Yes No -
23 De-activate circle identification Yes No -
24 Circle identification with 0 and 90 degrees Yes No -