EasyManuals Logo

SMC Networks LECSB2-T Series User Manual

SMC Networks LECSB2-T Series
945 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #876 background imageLoading...
Page #876 background image
17 - 20
17Positioning mode (pushing operation)
17.7.3 Point table
Point table method when using the pushing operation, set each value of the point table using the setup
software (MR Configurator2
TM
) or the operation unit.
The following describes an example of pushing operation divided into the following three steps.
<STEP1> In positioning operation, move from Positioning start position to Pushing start position
(operation of point table 1)
<STEP2> In the pushing operation, perform the pushing operation to the pushing object (operation of
point table 2).
<STEP3> Return to Positioning start position in positioning operation
(operation of point table 3)
Assign a point table for each of the above STEPs.
Point
table No.
Position data /
Pushing limit
position
[10^stm μm]
Servo motor rotation
speed / speed limit
value
[r/min]
Acceleration
time
constant
[ms]
Deceleration
time
constant
[ms]
Dwell
[ms]
Auxiliary
function
M code
Pushing
torque
[0.1%]
STEP1
1
8.00
3000
100
150
0(Note2)
1
0(Note4)
0(Note5)
STEP2
2
12.00
500
0(Note1)
0(Note1)
0(Note3)
16
0(Note4)
500
STEP3
3
0
2000
100
300
0
0
15
0(Note5)
Note1Set the auxiliary function to "1", "3", "8" or "9" and perform continuous operation when dwell = 0.
At this time, the acceleration time constant and deceleration time constant data selected when
starting position data are valid The acceleration time constant and deceleration time constant of
the following point tables are disabled.
Note2When performing the pushing operation, always set the dwell of the point table data immediately
before the pushing operation to “0”.
If you set a value other than “0”, [AL7F.4 Pushing start error] will occur.
Note3When "0", "2", "16" or "18" is set for the auxiliary function, the dwell of this point table No is
disabled.
Note4When the point table number including the pushing operation is started, no M code is output.
Note5If a value other than "16" or "18" is set for the auxiliary function, the pushing torque of this point
table No will be disabled.
The positioning operation using the point table number selected when ST1 (start signal) is turned on, and
the pushing operation using consecutive point table numbers are performed. After reaching the pushing
torque, confirm that INP is turned on, and select and start the next point table. At this time, the pushing
operation is continued (the pushing torque is continued) until ST1 is entered.
pushing
object
pushing
object
pushing
object
Motor
Motor
Motor
position address
position address
position address
Table
Table
Table
Ball screw
Ball screw
Ball screw
pushing torque 50%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks LECSB2-T Series and is the answer not in the manual?

SMC Networks LECSB2-T Series Specifications

General IconGeneral
BrandSMC Networks
ModelLECSB2-T Series
CategoryDC Drives
LanguageEnglish