EasyManuals Logo
Home>SMC Networks>DC Drives>LECSB2-T Series

SMC Networks LECSB2-T Series User Manual

SMC Networks LECSB2-T Series
945 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #576 background imageLoading...
Page #576 background image
16 - 76
16. POSITIONING MODE
16.4.5 Point table setting
Set the data for operation to the point table. The following shows the items to be set.
Item
Main description
Position data
Set the position data for movement.
Servo motor
speed
Set the command speed of the servo motor for execution of positioning.
Acceleration
time constant
Set the acceleration time constant.
Deceleration
time constant
Set the deceleration time constant.
Dwell
Set the waiting time when performing automatic continuous operation.
Auxiliary function
Set when performing automatic continuous operation.
M code
Outputs the first digit and the second digit of the M code in 4-bit binary
respectively.
Refer to section 4.2.2 for details of the point table.
16.4.6 Actual operation
Start actual operation after confirmation of normal operation by test operation and completion of the
corresponding parameter settings.
16.4.7 Troubleshooting at start-up
CAUTION
Never make a drastic adjustment or change to the parameter values as doing so
will make the operation unstable.
POINT
Using Setup software (MR Configurator2
TM
), you can refer to the reason for
rotation failure, etc.
The following faults may occur at start-up. If any of such faults occurs, take the corresponding action.
No.
Start-up sequence
Fault
Investigation
Possible cause
Reference
1
Power on
The 7-segment LED
display does not turn
on.
The 7-segment LED
display flickers.
Not improved even if CN1, CN2,
and CN3 connectors are
disconnected.
1. Power supply voltage fault
2. The driver is malfunctioning.
Improved when CN1 connector is
disconnected.
Power supply of CN1 cabling is
shorted.
Improved when CN2 connector is
disconnected.
1. Power supply of encoder
cabling is shorted.
2. Encoder is malfunctioning.
Improved when CN3 connector is
disconnected.
Power supply of CN3 cabling is
shorted.
Alarm occurs.
Refer to chapter 8 and remove the cause.
Chapter 8
(Note)
2
Switch on SON
(Servo-on).
Alarm occurs.
Refer to chapter 8 and remove the cause.
Chapter 8
(Note)
Servo motor shaft is
not servo-locked.
(Servo motor shaft is
free.)
1. Check the display to see if the
driver is ready to operate.
2. Check the external I/O signal
indication (section 3.1.7 or
3.2.7) to see if SON (Servo-
on) is on.
1. SON (Servo-on) is not input.
(wiring mistake)
2. 24 V DC power is not supplied
to DICOM.
Section
3.1.7
Section
3.2.7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks LECSB2-T Series and is the answer not in the manual?

SMC Networks LECSB2-T Series Specifications

General IconGeneral
BrandSMC Networks
ModelLECSB2-T Series
CategoryDC Drives
LanguageEnglish