SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the normalization characteristic for the analog outputs.
The normalization characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 2nd value pair of the
characteristic.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency: The unit of this parameter (V or mA) depends on the analog input type.
Refer to: p0776
Notice: This parameter is automatically overwritten when the analog output type is changed (p0776).
Note: This parameter is automatically overwritten if p0776 (type of analog output) is changed.
The parameters for the characteristic do not have a limiting effect.
Description: Sets the signal source to invert the analog output signals.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Note: AO: Analog Output
T: Terminal
Description: Displays the status of analog outputs.
Note: AO: Analog Output
p0780[0...1] CU analog outputs characteristic value y2 / CU char y2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
-20.000 [V] 20.000 [V] 20.000 [V]
p0782[0...1] BI: CU analog outputs signal source for inversion / CU AO invert
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
- - 0
r0785.0...1 BO: CU analog outputs status word / CU AO status word
Access level: 3 Calculated: - Data type: Unsigned16
Unit: - Scaling: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Analog output AO0 is negative Yes No -
01 Analog output AO1 is negative Yes No -