List of Parameters
Parameters
1-145
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the signal source for control word 1 bit 5 (continue ramp-function generator/freeze ramp-function generator).
Dependency: Refer to: r0054, p1140, p1142
Notice: The ramp-function generator is, independent of the state of the signal source, active in the following cases:
- OFF1/OFF3.
- ramp-function generator output within the suppression bandwidth.
- ramp-function generator output below the minimum speed.
Note: Bit 5 = 0: Freeze ramp-function generator
Bit 5 = 1: Continue ramp-function generator
Description: Sets the signal source for control word 1 bit 6 (enable setpoint/disable setpoint).
Dependency: Refer to: p1140, p1141
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 6 = 0: Inhibit setpoint (the ramp-function generator input is set to zero)
Bit 6 = 1: Enable setpoint
Description: Sets the signal source for control word 1 bit 6 (enable setpoint/disable setpoint).
Dependency: Refer to: p1140, p1141
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 6 = 0: Inhibit setpoint (the ramp-function generator input is set to zero)
Bit 6 = 1: Enable setpoint
p1141[0...n] BI: Continue ramp-function generator / Continue RFG
CU230P-2 DP Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 2090.5
p1142[0...n] BI: Speed setpoint enable / n_set enable
CU230P-2 CAN
CU230P-2 HVAC
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 1
p1142[0...n] BI: Speed setpoint enable / n_set enable
CU230P-2 DP Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 2090.6