EasyManua.ls Logo

Siemens CU230P-2 DP - Fig. 2-44 2505 - Control word, setpoint channel

Siemens CU230P-2 DP
668 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Internal control/status words
Function diagrams
2-489
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Fig. 2-44 2505 – Control word, setpoint channel
- 2505 -
Function diagram
87654321
FP_2505_97_51.vsd
Internal control/status words
G120 CU230P-2
29.10.2009 V4.3
Control word, setpoint channel
11
12
13
14
15
9
10
8
7
6
5
4
3
2
1
0
r1198.3
r1198.5
r1198.6
r1198.11
r1198.13
r1198.14
r1198.2
r1198.1
r1198.0
r1198.15
(722.3)
n_set_fixed Bit 0
p1020 [C]
(722.4)
n_set_fixed Bit 1
p1021 [C]
(722.5)
n_set_fixed Bit 2
p1022 [C]
(0)
n_set_fixed Bit 3
p1023 [C]
(0)
Mop raise
p1035 [C]
(0)
Mop lower
p1036 [C]
(0)
Bypass RFG
p1122 [C]
Control word, setpoint channel (r1198)
1 = Fixed setpoint, bit 0
1 = Fixed setpoint, bit 1
1 = Fixed setpoint, bit 2
1 = Fixed setpoint, bit 3
Reserved
1 = Inhibit negative direction of rotation
1 = Inhibit positive direction of rotation
Reserved
Reserved
Reserved
Reserved
1 = Dir of rot reversal
Reserved
1 = Motorized potentiometer, raise
1 = Motorized potentiometer, lower
1 = Bypass ramp-function generator
To fixed speed setpoints [3010.2]
To fixed speed setpoints [3010.2]
To fixed speed setpoints [3010.2]
To fixed speed setpoints [3010.2]
To direction of rotation limiting and
direction of rotation reversal [3040.3]
To direction of rotation limiting and
direction of rotation reversal [3040.5]
To direction of rotation limiting and
direction of rotation reversal [3040.2]
To the motorized potentiometer [3020.1]
To the motorized potentiometer [3020.1]
To the setpoint channel [3060.1] [3070.3]
STW setpoint chan
r1198
r1198
Bit No.
(0)
Inhib neg dir
p1110 [C]
(0)
Inhib pos dir
p1111 [C]
(722.1)
Setp inv
p1113 [C]