Siemens CU230P-2 DP - p3888 ESM reset number of activations and faults; ESM reset act flts; r3889.0...6 CO;BO: ESM status word; ESM status word; p3900 Completion of quick commissioning; Compl quick_comm

Siemens CU230P-2 DP
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-297
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Resets the number of activations of emergency operation and the number of faults which have occurred (in r3887).
0 = Do not reset
1 = Reset
Description: Displays the status word for emergency operation (ESM).
Description: Exits quick commissioning (p0010 = 1) with automatic calculation of all parameters of all existing drive data sets
that depend on the entries made during quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning.
The interconnections of PROFIBUS PZD telegram selection (p0922) and the interconnections via p0700, p1000
and p1500 are re-established and all of the dependent motor, open-loop and control-loop control parameters are
calculated (corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p0700, p1000 and p1500 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the calculations associated with the motor, open-loop and closed-loop control parameters
corresponding to p0340 = 1.
Value: 0: No quick parameterization
1: Quick parameterization after parameter reset
2: Quick parameterization (only) for BICO and motor parameters
3: Quick parameterization for motor parameters (only)
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note: When the calculations have been completed, p3900 and p0010 are automatically reset to a value of 0.
When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters associ-
ated with a selected Siemens catalog motor are not overwritten.
If a catalog motor has not been selected (see p0300), then the following parameters are reset with p3900 > 0 in
order to restore the situation that applied when commissioning the drive for the first time:
for induction motors p0320, p0352, p0362 ... p0369, p0604, p0605, p0626 ... p0628.
for synchronous motors p0326, p0327, p0352, p0604, p0605.
p3888 ESM reset number of activations and faults / ESM reset act flts
Access level: 4 Calculated: - Data type: Unsigned8
Can be changed: T Scaling: - Data set: -
Min Max Factory setting
0 1 0
r3889.0...6 CO/BO: ESM status word / ESM status word
Access level: 3 Calculated: - Data type: Unsigned32
Unit: - Scaling: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Emergency operation (ESM) active Yes No -
01 Inversion of the direction of rotation Yes No -
02 Setpoint signal lost Yes No -
03 Technology controller actual value (p2264)
lost
Yes No -
04 Bypass active Yes No -
05 ESM setpoint technology controller parame-
terized (p3884)
Yes No -
06 Technology controller active during emer-
gency operation
Yes No -
p3900 Completion of quick commissioning / Compl quick_comm
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1) Scaling: - Data set: -
Min Max Factory setting
0 3 0