Siemens CU230P-2 DP - p11258 Free tec_ctrl 2 setpoint ramp-down time; Ftec2 setp t_r�dn; r11260 CO: Free tec_ctrl 2 setpoint after ramp-function generator; Ftec2 setp aft RFG; p11264 CI: Free tec_ctrl 2 actual value signal source; Ftec2 act v s_s; p11265 Free tec_ctrl 2 actual value smoothing time constant; Ftec2 act v T

Siemens CU230P-2 DP
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-345
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the ramp-down time of the free technology controller 2.
Dependency: Refer to: p11257
Note: The ramp-down time is referred to 100%.
Description: Display and connector output for the setpoint after the ramp-function generator of the free technology controller 2.
Description: Sets the signal source for the actual value of the free technology controller 2.
Description: Sets the smoothing time constant (PT1) for the actual value of the free technology controller 2.
Description: Sets the upper limit for the actual value signal of the free technology controller 2.
Dependency: Refer to: p11264
Description: Sets the lower limit for the actual value signal of the free technology controller 2.
Dependency: Refer to: p11264
Description: Sets the inversion of the actual value signal of the free technology controller 2.
Value: 0: No inversion
1: Inversion
p11258 Free tec_ctrl 2 setpoint ramp-down time / Ftec2 setp t_r-dn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
0.00 [s] 650.00 [s] 1.00 [s]
r11260 CO: Free tec_ctrl 2 setpoint after ramp-function generator / Ftec2 setp aft RFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Unit: [%] Scaling: PERCENT Data set: -
p11264 CI: Free tec_ctrl 2 actual value signal source / Ftec2 act v s_s
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Min Max Factory setting
- - 0
p11265 Free tec_ctrl 2 actual value smoothing time constant / Ftec2 act v T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
0.00 [s] 60.00 [s] 0.00 [s]
p11267 Free tec_ctrl 2 actual value upper limit / Ftec2 act v up lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p11268 Free tec_ctrl 2 actual value lower limit / Ftec2 act v lo lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p11271 Free tec_ctrl 2 actual value inversion / Ftec2 act v inv
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Min Max Factory setting
0 1 0