List of Parameters
Parameters
1-345
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the ramp-down time of the free technology controller 2.
Dependency: Refer to: p11257
Note: The ramp-down time is referred to 100%.
Description: Display and connector output for the setpoint after the ramp-function generator of the free technology controller 2.
Description: Sets the signal source for the actual value of the free technology controller 2.
Description: Sets the smoothing time constant (PT1) for the actual value of the free technology controller 2.
Description: Sets the upper limit for the actual value signal of the free technology controller 2.
Dependency: Refer to: p11264
Description: Sets the lower limit for the actual value signal of the free technology controller 2.
Dependency: Refer to: p11264
Description: Sets the inversion of the actual value signal of the free technology controller 2.
Value: 0: No inversion
1: Inversion
p11258 Free tec_ctrl 2 setpoint ramp-down time / Ftec2 setp t_r-dn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
0.00 [s] 650.00 [s] 1.00 [s]
r11260 CO: Free tec_ctrl 2 setpoint after ramp-function generator / Ftec2 setp aft RFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Unit: [%] Scaling: PERCENT Data set: -
p11264 CI: Free tec_ctrl 2 actual value signal source / Ftec2 act v s_s
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Min Max Factory setting
- - 0
p11265 Free tec_ctrl 2 actual value smoothing time constant / Ftec2 act v T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
0.00 [s] 60.00 [s] 0.00 [s]
p11267 Free tec_ctrl 2 actual value upper limit / Ftec2 act v up lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p11268 Free tec_ctrl 2 actual value lower limit / Ftec2 act v lo lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p11271 Free tec_ctrl 2 actual value inversion / Ftec2 act v inv
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Min Max Factory setting
0 1 0