SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the signal source for the 1st OC/OFF2.
The AND logic operation of the 1st OC/OFF2 and 2nd OC/OFF2 results in control word 1, bit 1 (OC/OFF2).
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 1 = 0: OC/OFF2 (immediate pulse suppression and switching on inhibited)
Bit 1 = 1: No OC/OFF2 (enable is possible)
OC: Operating condition
Description: Sets the signal source for the 1st OC/OFF2.
The AND logic operation of the 1st OC/OFF2 and 2nd OC/OFF2 results in control word 1, bit 1 (OC/OFF2).
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 1 = 0: OC/OFF2 (immediate pulse suppression and switching on inhibited)
Bit 1 = 1: No OC/OFF2 (enable is possible)
OC: Operating condition
Description: Sets the signal source for the 2nd OC/OFF2.
The AND logic operation of the 1st OC/OFF2 and 2nd OC/OFF2 results in control word 1, bit 1 (OC/OFF2).
Note: Bit 1 = 0: OC/OFF2 (immediate pulse suppression and switching on inhibited)
Bit 1 = 1: No OC/OFF2 (enable is possible)
OC: Operating condition
p0844[0...n] BI: 1. OFF2 / 1. OFF2
CU230P-2 CAN
CU230P-2 HVAC
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 1
p0844[0...n] BI: 1. OFF2 / 1. OFF2
CU230P-2 DP Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 2090.1
p0845[0...n] BI: 2. OFF2 / 2. OFF2
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 1