Parameters
List of Parameters
1-188
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the source for the torque setpoint.
For single-digit values, the following applies:
The value specifies the main setpoint.
For double-digit values, the following applies:
The left-hand digit specifies the supplementary setpoint, the right-hand digit the main setpoint.
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value: 0: No main setpoint
2: Analog setpoint
6: Fieldbus
7: Analog setpoint 2
20: Analog setpoint + no main setpoint
22: Analog setpoint + analog setpoint
26: Analog setpoint + fieldbus
27: Analog setpoint + analog setpoint 2
60: Fieldbus + no main setpoint
62: Fieldbus + analog setpoint
66: Fieldbus+fieldbus
67: Fieldbus + analog setpoint 2
70: Analog setpoint 2 + no main setpoint
72: Analog setpoint 2 + analog setpoint
76: Analog setpoint 2 + fieldbus
77: Analog setpoint 2 + analog setpoint 2
Dependency: When changing this parameter, the following settings are influenced:
Refer to: p1503, p1511
Note: With PROFIBUS / PROFINET Control Units, p0922 = 999 must be set so that the command and setpoint sources
can be changed.
p1500[0...n] Torque setpoint selection / M_set sel
CU230P-2 DP Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(1), T Scaling: - Data set: CDS, p0170
Min Max Factory setting
0 77 6