EasyManua.ls Logo

Siemens CU230P-2 DP - Fig. 2-46 2511 - Status word 2 (r0053)

Siemens CU230P-2 DP
668 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Internal control/status words
Function diagrams
2-491
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Fig. 2-46 2511 – Status word 2 (r0053)
- 2511 -
Function diagram
87654321
FP_2511_97_51.vsd
Internal control/status words
G120 CU230P-2
29.10.2009 V4.3
Status word 2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
ZSW 2
r0053
r0053
1 = DC brake active
0 = DC brake not active
Bit No. Status word 2 (r0053)
1 = |n_act| > p1226 (n_standstill)
1 = |n_act| > p1080 (n_min)
1 = I_act >= p2170
1 = |n_act| > p2155
1 = |n_act| <= p2155
1 = |n_act| >= r1119 (f_set)
1 = Vdc <= p2172
1 = Vdc > p2172
1 = Ramping finished
1 = Techn. contr. out at lower limit
1 = Techn. contr. out at upper limit
Reserved
Reserved
DC brake ZSW
r1239
r1239
Reserved
Reserved
ZSW monitor 1
r2197
r2197
ZSW monitor 1
r2197
r2197
ZSW monitor 1
r2197
r2197
ZSW monitor 1
r2197
r2197
ZSW monitor 1
r2197
r2197
ZSW monitor 1
r2197
r2197
ZSW monitor 1
r2197
r2197
ZSW monitor 1
r2197
r2197
.8
.5
.0
.8
.2
.1
.4
.9
.10
RFG ZSW
r1199
r1199
Tec_ctrl stat word
r2349
r2349
Tec_ctrl stat word
r2349
r2349
.10
.11
.2
r0053.0
r0053.1
r0053.4
r0053.5
r0053.11
r0053.2
r0053.6
r0053.9
r0053.3
r0053.7
r0053.8
r0053.10
[7017.5]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[3080.7]
[7958.7]
[7958.7]
<1>
<1>
Only with Power Module PM240

Table of Contents