Parameters
List of Parameters
1-170
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the open and closed loop control mode of a drive.
Value: 0: V/f control with linear characteristic
1: V/f control with linear characteristic and FCC
2: V/f control with parabolic characteristic
3: V/f control with parameterizable characteristic
4: V/f control with linear characteristic and ECO
5: V/f control for drives requiring a precise freq. (e.g. textiles)
6: V/f control for drives requiring a precise frequency and FCC
7: V/f control for a parabolic characteristic and ECO
19: V/f control with independent voltage setpoint
20: Speed control (encoderless)
22: Torque control (encoderless)
Dependency: Only operation with V/f characteristic is possible if the rated motor speed is not entered (p0311).
Operation with a V/f characteristic is not supported for 1LE4 synchronous motors.
Refer to: p0300, p0311, p1501
Notice: Active slip compensation is required in the V/f control types with Eco mode (p1300 = 4, 7). The scaling of the slip
compensation (p1335) should be set so that the slip is completely compensated (generally 100%).
The Eco mode is only effective in steady-state operation and when the ramp-function generator is not bypassed. In
the case of analog setpoints, if required the tolerance for ramp-up and ramp-down should be actively increased for
the ramp-function generator using p1148 in order to reliably signal a steady-state condition.
Note: Only by selecting closed-loop speed control (p1300 = 20) is it possible to change over in opertaion to closed-loop
torque control (p1501). At the changeover, the setting of p1300 does not change. In this case, the actual state is
displayed in r1407, bit 2 and bit 3.
For the open-loop control modes p1300 = 5 and 6 (textile sector), slip compensation p1335, resonance damping
p1338, and the Imax frequency controller are switched off internally so that the output frequency can be set pre-
cisely. The Imax voltage controller remains active.
During operation (the pulses enabled) the open-loop/closed-loop control mode cannot be changed by changing
over drive data sets.
p1300[0...n] Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(1), T Scaling: - Data set: DDS, p0180
Min Max Factory setting
0 22 0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU230P-2 DP and is the answer not in the manual?

Siemens CU230P-2 DP Specifications

General IconGeneral
BrandSiemens
ModelCU230P-2 DP
CategoryControl Unit
LanguageEnglish

Related product manuals