List of Parameters
Parameters
1-337
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the ramp-down time for the free technology controller 0.
Dependency: Refer to: p11057
Note: The ramp-down time is referred to 100 %.
Description: Display and connector output for the setpoint after the ramp-function generator of the free technology controller 0.
Description: Sets the signal source for the actual value of the free technology controller 0.
Description: Sets the smoothing time constant (PT1) for the actual value of the free technology controller 0.
Description: Sets the upper limit for the actual value signal of the free technology controller 0.
Dependency: Refer to: p11064
Description: Sets the lower limit for the actual value signal of the free technology controller 0.
Dependency: Refer to: p11064
Description: Sets the inversion of the actual value signal of the free technology controller 0.
Value: 0: No inversion
1: Inversion
p11058 Free tec_ctrl 0 setpoint ramp-down time / Ftec0 setp t_r-dn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
0.00 [s] 650.00 [s] 1.00 [s]
r11060 CO: Free tec_ctrl 0 setpoint after ramp-function generator / Ftec0 setp aft RFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Unit: [%] Scaling: PERCENT Data set: -
p11064 CI: Free tec_ctrl 0 actual value signal source / Ftec0 act v s_s
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Min Max Factory setting
- - 0
p11065 Free tec_ctrl 0 actual value smoothing time constant / Ftec0 act v T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
0.00 [s] 60.00 [s] 0.00 [s]
p11067 Free tec_ctrl 0 actual value upper limit / Ftec0 act v up lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p11068 Free tec_ctrl 0 actual value lower limit / Ftec0 act v lo lim
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p11071 Free tec_ctrl 0 actual value inversion / Ftec0 act v inv
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Min Max Factory setting
0 1 0