Parameters
List of Parameters
1-190
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the signal source for the torque setpoint for torque control.
Note: A change is made to closed-loop torque control if, in p1300, closed-loop torque control was selected or if the selec-
tion was made using the changeover source in p1501.
it is also possible to change over in operation using p1501.
Description: Sets the signal source for the torque setpoint for torque control.
Note: A change is made to closed-loop torque control if, in p1300, closed-loop torque control was selected or if the selec-
tion was made using the changeover source in p1501.
it is also possible to change over in operation using p1501.
Description: Sets the signal source for the torque setpoint for torque control.
Note: A change is made to closed-loop torque control if, in p1300, closed-loop torque control was selected or if the selec-
tion was made using the changeover source in p1501.
it is also possible to change over in operation using p1501.
Description: Displays the torque setpoint before entering the supplementary torque.
For closed-loop speed control, r1508 corresponds to the speed controller output; for closed-loop torque control,
r1508 corresponds to the torque setpoint of the signal source assigned in p1503.
Description: Sets the signal source for supplementary torque 1.
Description: Sets the signal source for scaling the supplementary torque 1.
p1503[0...n] CI: Torque setpoint / M_set
CU230P-2 CAN Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2003 Data set: CDS, p0170
Min Max Factory setting
- - 0
p1503[0...n] CI: Torque setpoint / M_set
CU230P-2 DP Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2003 Data set: CDS, p0170
Min Max Factory setting
- - 2050[1]
p1503[0...n] CI: Torque setpoint / M_set
CU230P-2 HVAC Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2003 Data set: CDS, p0170
Min Max Factory setting
- - 755[0]
r1508 CO: Torque setpoint before supplementary torque / M_set bef. M_suppl
Access level: 2 Calculated: - Data type: FloatingPoint32
Unit: [Nm] Scaling: p2003 Data set: -
p1511[0...n] CI: Supplementary torque 1 / M_suppl 1
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2003 Data set: CDS, p0170
Min Max Factory setting
- - 0
p1512[0...n] CI: Supplementary torque 1 scaling / M_suppl 1 scal
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Data set: CDS, p0170
Min Max Factory setting
- - 0