List of Parameters
Parameters
1-293
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3111
Refer to: F07862
Description: Displays the status of NAMUR signal bit bar.
The faults or alarms are assigned to the appropriate signaling/message classes and influence a specific message
bit.
Description: Displays the fault value of the oldest active fault.
Description: Sets the signal source for the speed actual value of the load monitoring.
Dependency: Refer to: r2169, p2181, p2192, p2193, p3231
Refer to: A07920, A07921, A07922, F07923, F07924, F07925
Note: The parameter is only effective for p2193 = 2.
p3112[0...n] BI: External fault 3 enable negated / Ext flt 3 enab neg
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 0
r3113.0...15 CO/BO: NAMUR message bit bar / NAMUR bit bar
Access level: 3 Calculated: - Data type: Unsigned16
Unit: - Scaling: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fault drive converter data electronics / soft-
ware error
Yes No -
01 Line supply fault Yes No -
02 DC link overvoltage Yes No -
03 Fault drive converter power electronics Yes No -
04 Drive converter overtemperature Yes No -
05 Ground fault Yes No -
06 Motor overload Yes No -
07 Bus error Yes No -
08 External safety-relevant shutdown Yes No -
10 Error internal communications Yes No -
11 Infeed fault Yes No -
15 Other faults Yes No -
r3131 CO: Current fault value / Current flt value
Access level: 3 Calculated: - Data type: Integer32
Unit: - Scaling: - Data set: -
p3230[0...n] CI: Load monitoring, speed actual value / Load monit n_act
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Data set: CDS, p0170
Min Max Factory setting
- - 0