Parameters
List of Parameters
1-252
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Displays the system runtime in milliseconds when the alarm was cleared.
Dependency: Refer to: r2110, r2122, r2123, r2124, r2134, r2145, r2146, p8400
Notice: The time comprises r2146 (days) and r2125 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
Description: Selects the faults for which the acknowledge mode is to be changed
Dependency: Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2127
Notice: It is not possible to re-parameterize the acknowledge mode of a fault in the following cases:
- if there is no existing fault number.
- the message type is not "fault" (F).
- when a fault is present.
Description: Sets the acknowledge mode for selected fault.
Value: 1: Acknowledgment only using POWER ON
2: Ack IMMEDIATELY after the fault cause has been removed
Dependency: Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2126
Notice: It is not possible to re-parameterize the acknowledge mode of a fault in the following cases:
- if there is no existing fault number.
- the message type is not "fault" (F).
- when a fault is present.
Note: The acknowledge mode can only be changed for faults with the appropriate identification.
Example:
F12345 and acknowledge mode = POWER ON (IMMEDIATELY) --> The acknowledge mode can be changed from
POWER ON to IMMEDIATELY.
Description: Selects faults or alarms which can be used as trigger.
Dependency: Refer to: r2129
r2125[0...63] Alarm time removed in milliseconds / t_alarm res ms
Access level: 3 Calculated: - Data type: Unsigned32
Unit: [ms] Scaling: - Data set: -
p2126[0...19] Setting fault number for acknowledge mode / Fault_no ackn_mode
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
0 65535 0
p2127[0...19] Sets acknowledgement mode / Acknowledge mode
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
1 2 1
p2128[0...15] Selecting fault/alarm code for trigger / Message trigger
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
0 65535 0