List of Parameters
Parameters
1-193
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the signal source for the lower torque limit.
Dependency: Refer to: p1520, p1521, p1522
Danger: Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Description: Sets the scaling for the upper torque limit or the torque limit when motoring.
Dependency: p1400 bit 4 = 0: Upper / lower
p1400 bit 4 = 1: Motoring / regenerative
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
Description: Sets the scaling for the lower torque limit.
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
Description: Displays the upper torque limit of all torque limits without offset.
Dependency: Refer to: p1520, p1521, p1522, p1523, p1528, p1529
Description: Displays the lower torque limit of all torque limits without offset.
Dependency: Refer to: p1520, p1521, p1522, p1523, p1528, p1529
p1523[0...n] CI: Torque limit lower / M_max lower
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2003 Data set: CDS, p0170
Min Max Factory setting
- - 1521[0]
p1524[0...n] CO: Torque limit upper/motoring scaling / M_max up/mot scal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Min Max Factory setting
-2000.0 [%] 2000.0 [%] 100.0 [%]
p1525[0...n] CO: Torque limit lower scaling / M_max lower scal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Min Max Factory setting
-2000.0 [%] 2000.0 [%] 100.0 [%]
r1526 CO: Torque limit upper without offset / M_max up w/o offs
Access level: 3 Calculated: - Data type: FloatingPoint32
Unit: [Nm] Scaling: p2003 Data set: -
r1527 CO: Torque limit lower without offset / M_max low w/o offs
Access level: 3 Calculated: - Data type: FloatingPoint32
Unit: [Nm] Scaling: p2003 Data set: -