Description: Displays the operating hours for the external motors.
The display can only be reset to zero.
Index: [0] = Motor 1
[1] = Motor 2
[2] = Motor 3
Description: Time limit for the continuous operation of external motors.
Continuous operation is measured starting from when a motor is connected to the line voltage. It ends when a
motor is disconnected from the line.
Description: Limit for the total operating time of external motors.
The total operating time of an external motor increases every time it is switched in.
r2379.0...7 CO/BO: Staging status word / Staging ZSW
Access level: 3 Calculated: - Data type: Unsigned32
Unit: - Scaling: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Start external motor 1 Yes No -
01 Start external motor 2 Yes No -
02 Start external motor 3 Yes No -
03 Staging enabled Yes No -
04 Staging/Destaging active Yes No -
05 All motors active Yes No -
06 AutoChange not possible Yes No -
07 Staging alarm active Yes No -
p2380[0...2] Staging operating hours / Staging op_hrs
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
0.0 [h] 340.28235E36 [h] 0.0 [h]
p2381 Staging time limit for continuous operation / Stag t_max cont
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
0.1 [h] 100000.0 [h] 24.0 [h]
p2382 Staging absolute operating time limit / Staging t_max op
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
0.1 [h] 100000.0 [h] 24.0 [h]