Siemens CU230P-2 DP - Fig. 2-126 8017 - Thermal I2 t motor model (PEM, p0300 = 2 xx)

Siemens CU230P-2 DP
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function diagrams
Signals and monitoring functions
2-578
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Fig. 2-126 8017 – Thermal I2t motor model (PEM, p0300 = 2xx)
- 8017 -
Function diagram
87654321
FP_8017_97_51.vsd
Signals and monitoring functions
G120 CU230P-2
29.10.2009 V4.3
Thermal I²t motor model (PEM, p0300 = 2xx)
<1>
0
1
0
1
[8016.5]
<1>
[8016.6]
<2>
<2>
Thermal
I²t motor model
(only for synchronous
machine)
A07012
"I²t-motor model overtemperature"
Only if there is a temperature sensor (p0601 = 2).
Only if <1> are not met.
Therm Mot_mod conf
- ... -
p0612 [D] (0010 bin)
Mot T_ambient
-40 ... 80 [°C]
p0625 [D] (20)
Mot I_standstill
0.00 ... 10000.00 [Aeff]
p0318 [D] (0.00)
I2t mot_mod T
0 ... 20000 [s]
p0611 [D] (0)
r0035
Mot_temp [°C]
Motor utilization [%]
r0034
Mot_temp flt thr
0.0 ... 240.0 [°C]
p0605 [D] (145.0)
model
I2t mot_mod thresh
0.0 ... 220.0 [°C]
p0615 [D] (180.0)
not smoothed
r0068
I_act abs val [Aeff]
[0]
–40 K
p0605 – 40 K
x 100 [%]
model

Table of Contents