Siemens CU230P-2 DP - p0852[0...n] BI: Operation enable; Operation enable; p0854[0...n] BI: Master ctrl by PLC; Master ctrl by PLC

Siemens CU230P-2 DP
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-112
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the signal source for control word 1 bit 3 (enable operation)
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 3 = 0: Inhibit operation (cancel pulses)
Bit 3 = 1: Enable operation (pulses can be enabled)
Description: Sets the signal source for control word 1 bit 3 (enable operation)
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 3 = 0: Inhibit operation (cancel pulses)
Bit 3 = 1: Enable operation (pulses can be enabled)
Description: Sets the signal source for control word 1 bit 10 (master control by PLC).
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 10 = 0: No master control by PLC
Bit 10 = 1: Master control by PLC
This bit is used to initiate a response for the drives when the control fails (F07220). If there is no control available,
then BI: p0854 should be set to a 1 signal.
If a control is available, control word 1 bit 10 = 1 (STW1.10, PZD1) must be set so that the received data is updated.
This applies regardless of the setting in p0854 and even in the case of free telegram configuration (p0922 = 999).
p0852[0...n] BI: Operation enable / Operation enable
CU230P-2 CAN
CU230P-2 HVAC
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 1
p0852[0...n] BI: Operation enable / Operation enable
CU230P-2 DP Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 2090.3
p0854[0...n] BI: Master ctrl by PLC / Master ctrl by PLC
CU230P-2 CAN
CU230P-2 HVAC
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 1