List of Parameters
Parameters
1-71
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Selects the function for digital input 0.
Value: 0: No pre-assignment
1: ON/OFF1
3: 2. OFF2
4: 2. OFF3
9: 2. Acknowledge faults
10: Jog bit 0
11: Jog bit 1
12: Direction reversal
13: Motorized potentiometer setpoint raise
14: Motorized potentiometer lower setpoint
15: Fixed speed setpoint selection Bit 0
16: Fixed speed setpoint selection Bit 1
17: Fixed speed setpoint selection Bit 2
18: Fixed speed setpoint selection Bit 3
26: Activate emergency operation
27: Enable technology controller
29: External fault 1
35: Command data set selection CDS bit 0
50: Load monitoring failure detection
Warning: It is possible to interconnect the digital input with several signal sinks using BICO parameterization without this
parameter providing a message. As a result of the corresponding BICO parameterization, for example, the drive
could undesirably accelerate without this function having been selected in this parameter.
Note: When changing the function within the selection possibilities, the previously selected interconnection is discon-
nected by resetting the signal sink.
However, the selected function is protected against being changed by BICO parameterization, i.e. the signal sink
must first be enabled using "no pre-assignment" before it can be interconnected again.
p0701[0...n] Pre-assignment digital input 0 / Pre-assignment DI0
PM230
PM250
PM260
CU230P-2 CAN
CU230P-2 HVAC
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
0 50 1