List of Parameters
Parameters
1-107
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the signal source to select the Command Data Set bit 1 (CDS bit 1).
Dependency: Refer to: r0050, p0810, r0836
Note: The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
Description: Copies one Drive Data Set (DDS) into another.
Index: [0] = Source Drive Data Set
[1] = Target Drive Data Set
[2] = Start copying procedure
Note: Procedure:
1. In Index 0, enter which drive data set is to be copied.
2. In Index 1, enter the drive data set data that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0819[2] is automatically set to 0 when copying is completed.
Description: Sets the signal source to select the Drive Data Set, bit 0 (DDS, bit 0).
Dependency: Refer to: r0051, p0826, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to select the Drive Data Set, bit 1 (DDS, bit 1).
Dependency: Refer to: r0051, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0811 BI: Command data set selection CDS bit 1 / CDS select., bit 1
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: -
Min Max Factory setting
- - 0
p0819[0...2] Copy Drive Data Set DDS / Copy DDS
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: C(15) Scaling: - Data set: -
Min Max Factory setting
0 3 0
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: C(15), T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 0
p0821[0...n] BI: Drive Data Set selection DDS bit 1 / DDS select., bit 1
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: C(15), T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 0