Parameters
List of Parameters
1-344
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the signal source to switch in/switch out the free technology controller 2.
1 signal: The technology controller is switched in.
0 signal: The technology controller is switched out.
Description: Sets the sampling time for the free technology controller 2.
Value: 0: Reserved
1: 128 ms
2: 256 ms
3: 512 ms
4: 1024 ms
Description: Displays the status word of the free technology controller 2.
Description: Sets the signal source for the setpoint of the free technology controller 2.
Description: Sets the ramp-up time for the free technology controller 2.
Dependency: Refer to: p11258
Note: The ramp-up time is referred to 100%.
p11200 BI: Free tec_ctrl 2 enable / Ftec2 enab
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
- - 0
p11228 Free tec_ctrl 2 sampling time / Ftec2 t_samp
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Min Max Factory setting
0 4 2
r11249.0...11 CO/BO: Free tec_ctrl 2 status word / Ftec2 stat_word
Access level: 3 Calculated: - Data type: Unsigned32
Unit: - Scaling: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Deactivated Yes No -
01 Limited Yes No -
08 Actual value at the minimum Yes No -
09 Actual value at the maximum Yes No -
10 Output at the minimum Yes No -
11 Output at the maximum Yes No -
p11253 CI: Free tec_ctrl 2 setpoint signal source / Ftec2 setp s_src
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: -
Min Max Factory setting
- - 0
p11257 Free tec_ctrl 2 setpoint ramp-up time / Ftec2 setp t_r-up
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: -
Min Max Factory setting
0.00 [s] 650.00 [s] 1.00 [s]