List of Parameters
Parameters
1-151
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: The value influences the rate at which the output frequency is changed during a flying restart . A higher value
results in a longer search time.
Caution: An unfavorable parameter value can result in the motor behaving in an uncontrollable fashion.
For vector control, a value that is too low or too high can cause flying restart to become unstable.
Note: The parameter factory setting is selected so that standard induction motors that are rotating can be found and
restarted as quickly as possible (fast flying restart).
With this presetting, if the motor is not found (e.g. for motors that are accelerated as a result of active loads) we rec-
ommend that the search rate is reduced (by increasing p1203).
Description: Displays the status for checking and monitoring flying restart states in the V/f control mode.
p1203[0...n] Flying restart search rate factor / FlyRst v_Srch Fact
PM240
PM250, PM260
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Min Max Factory setting
10 [%] 4000 [%] 100 [%]
r1204.0...13 CO/BO: Flying restart, V/f control status / FlyRest Vf st
Access level: 4 Calculated: - Data type: Unsigned16
Unit: - Scaling: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Current impressed Yes No -
01 No current flow Yes No -
02 Voltage input Yes No -
03 Voltage reduced Yes No -
04 Start ramp-function generator Yes No -
05 Wait for execution Yes No -
06 Slope filter act Yes No -
07 Positive gradient Yes No -
08 Current < thresh Yes No -
09 Current minimum Yes No -
10 Search in the positive direction Yes No -
11 Stop after positive direction Yes No -
12 Stop after negative direction Yes No -
13 No result Yes No -