Fig. 2-115 7978 – Hibernation
- 7978 -
Function diagram
87654321
FP_7978_97_01.vsd
Technology functions
G120 CU230P-2
29.10.2009 V4.3
Hibernation
%
t
x
Hib start w Tec_c
0.000 ... 200.000 [%]
p2392 (0.000)
Minimum speed
000 ... 19500.000 [1/min]
p1080 [D] (0.000)
Hib n_Boost
000 ... 21000.000 [1/min]
p2395 [D] (0.000)
t
y
Hib t_del
0 ... 3599 [s]
p2391 [D] (120)
Hib t_Boost
0 ... 3599 [s]
p2394 [D] (0)
Hib t_shutd max
0 ... 863999 [s]
p2396 [D] (0)
Hib n_Start
000 ... 21000.000 [1/min]
p2390 [D] (0.000)
f
t
t
PID
0
Hib ZSW
r2399
r2399
Technology error signal
<6>
Setting p2200 = 1, p2251 = 0, p2398 = 1, p2394 > 0
(Hibernation with boost using the technology setpoint as the main setpoint)
<5>
<4>
<2>
<1>
<3>
<1>
Technology setpoint as main setpoint<2>
Hibernation boost speed p2395<3>
Hibernation restart speed = (p1080+p2390) * 1.05<4>
Hibernation starting speed = p1080 + p2390<5>
Hibernation boost time period p2394 = 0 --> no boost
<6>
Hibernation active
t
x
=
p2395
p1082
p1121
Technology setpoint
Hibernation restart value with technology controller p2392
t
y
=
(p1080+p2390)
p1082
p1120
1.05
Hib op_mode
0 ... 1
p2398 (0)
t
x
Minimum speed
0.000 ... 19500.000 [1/min]
p1080 [D] (0.000)
t
y
Hib t_del
0 ... 3599 [s]
p2391 [D] (120)
Hib t_shutd max
0 ... 863999 [s]
p2396 [D] (0)
Hib n_Start
0.000 ... 21000.000 [1/min]
p2390 [D] (0.000)
f
t
t
0
Setting p2200 = 0, p2251 = 0,1, p2398 = 1, p2394 = 0
(Hibernation without boost using an external setpoint)
<5>
<4>
Hibernation restart speed = p1080+p2390+p2393<4>
Hibernation starting speed = p1080 + p2390<5>
Hibernation active
t
x
=
p1080
p1082
p1121
t
y
=
(p1080+p2390+p2393)
p1082
p1120
Hib op_mode
0 ... 1
p2398 (0)
Hib st. w/o Tec_c
0.000 ... 21000.000 [1/min]
p2393 [D] (0.000)
r2397[0..1]
Hib n_outp act [1/min]
External setpoint
Speed setpoint
Inverter output
frequency
Hib ZSW
r2399
r2399
r2397[0..1]
Hib n_outp act [1/min]