List of Parameters
Parameters
1-135
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the signal source for scaling the supplementary setpoint.
Description: Displays the effective supplementary setpoint. The value shown is the additional setpoint after scaling.
Description: Displays the total effective setpoint. The value indicates the sum of the effective main setpoint and supplementary
setpoint.
Description: Sets the lowest possible speed/velocity. This value is not undershot in operation.
Note: The parameter value applies for both motor directions of rotation.
In exceptional cases, the motor can operate below this value (e.g. when reversing).
p1076[0...n] CI: Supplementary setpoint scaling / Suppl setp scal
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Data set: CDS, p0170
Min Max Factory setting
- - 1
r1077 CO: Supplementary setpoint effective / Suppl setpoint eff
Access level: 3 Calculated: - Data type: FloatingPoint32
Unit: [rpm] Scaling: p2000 Data set: -
r1078 CO: Total setpoint effective / Total setpoint eff
Access level: 3 Calculated: - Data type: FloatingPoint32
Unit: [rpm] Scaling: p2000 Data set: -
p1080[0...n] Minimum speed / Minimum speed
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C(1), T Scaling: - Data set: DDS, p0180
Min Max Factory setting
0.000 [rpm] 19500.000 [rpm] 0.000 [rpm]