Function diagrams
Data sets
2-588
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Fig. 2-134 8565 – Drive Data Sets (DDS)
- 8565 -
Function diagram
87654321
FP_8565_97_51.vsd
Data sets
G120 CU230P-2
29.10.2009 V4.3
Drive Data Sets (DDS)
DDS3
DDS2
DDS1
DDS0
r0837.1
r0051.1
<1>
<1>
A07530 "Drive data set does not exist"
A BICO interconnection to a parameter which is part of a drive data set always influences the currently effective data set.
(0)
DDS select., bit 0
p0820 [C]
(0)
DDS select., bit 1
p0821 [C]
DDS count
1 ... 4
p0180 (1)
DDS selected
r0837
r0837
.0
DDS effective
r0051
r0051
.0
Copy DDS, source
p0819[0] (0)
Copy DDS, start
p0819[2] (0)
Copy DDS, target
p0819[1] (1)
Note
Data sets can only be applied
and cleared when p0010 = 15
is set.