List of Parameters
Parameters
1-271
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the value for fixed value 11 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 12 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 13 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 14 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 15 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2211[0...n] CO: Technology controller, fixed value 11 / Tec_ctrl fix val11
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Min Max Factory setting
-200.00 [%] 200.00 [%] 110.00 [%]
p2212[0...n] CO: Technology controller, fixed value 12 / Tec_ctrl fix val12
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Min Max Factory setting
-200.00 [%] 200.00 [%] 120.00 [%]
p2213[0...n] CO: Technology controller, fixed value 13 / Tec_ctrl fix val13
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Min Max Factory setting
-200.00 [%] 200.00 [%] 130.00 [%]
p2214[0...n] CO: Technology controller, fixed value 14 / Tec_ctrl fix val14
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Min Max Factory setting
-200.00 [%] 200.00 [%] 140.00 [%]
p2215[0...n] CO: Technology controller, fixed value 15 / Tec_ctrl fix val15
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Min Max Factory setting
-200.00 [%] 200.00 [%] 150.00 [%]