Siemens CU230P-2 DP - p2211[0...n] CO: Technology controller, fixed value 11; Tec_ctrl fix val11; p2212[0...n] CO: Technology controller, fixed value 12; Tec_ctrl fix val12; p2213[0...n] CO: Technology controller, fixed value 13; Tec_ctrl fix val13; p2214[0...n] CO: Technology controller, fixed value 14; Tec_ctrl fix val14

Siemens CU230P-2 DP
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-271
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the value for fixed value 11 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 12 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 13 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 14 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 15 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2211[0...n] CO: Technology controller, fixed value 11 / Tec_ctrl fix val11
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Min Max Factory setting
-200.00 [%] 200.00 [%] 110.00 [%]
p2212[0...n] CO: Technology controller, fixed value 12 / Tec_ctrl fix val12
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Min Max Factory setting
-200.00 [%] 200.00 [%] 120.00 [%]
p2213[0...n] CO: Technology controller, fixed value 13 / Tec_ctrl fix val13
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Min Max Factory setting
-200.00 [%] 200.00 [%] 130.00 [%]
p2214[0...n] CO: Technology controller, fixed value 14 / Tec_ctrl fix val14
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Min Max Factory setting
-200.00 [%] 200.00 [%] 140.00 [%]
p2215[0...n] CO: Technology controller, fixed value 15 / Tec_ctrl fix val15
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Data set: DDS, p0180
Min Max Factory setting
-200.00 [%] 200.00 [%] 150.00 [%]