SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the second signal source to acknowledge faults.
Note: A fault acknowledgement is triggered with a 0/1 signal.
Description: Sets the third signal source to acknowledge faults.
Note: A fault acknowledgement is triggered with a 0/1 signal.
Description: Sets the signal source for external fault 1.
Dependency: Refer to: F07860
Note: An external fault is triggered with a 1/0 signal.
Description: Sets the signal source for external fault 2.
Dependency: Refer to: F07861
Note: An external fault is triggered with a 1/0 signal.
Description: Sets the signal source for external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p3110, p3111, p3112
Refer to: F07862
Note: An external fault is triggered with a 1/0 signal.
p2104[0...n] BI: 2. Acknowledge faults / 2. Acknowledge
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 722.2
p2105[0...n] BI: 3. Acknowledge faults / 3. Acknowledge
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 0
p2106[0...n] BI: External fault 1 / External fault 1
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 1
p2107[0...n] BI: External fault 2 / External fault 2
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 1
p2108[0...n] BI: External fault 3 / External fault 3
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 1