EasyManua.ls Logo

Siemens CU230P-2 DP - r0837.0...1 CO;BO: Drive Data Set DDS selected; DDS selected; p0840[0...n] BI: ON;OFF1; ON;OFF1

Siemens CU230P-2 DP
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-109
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Displays the drive data set (DDS) selected via the binector input.
Dependency: Refer to: r0051, p0820, p0821
Note: Drive data sets are selected via binector input p0820 and following.
The currently effective drive data set is displayed in r0051.
If there is only one data set, then a value of 0 is displayed in this parameter and not the selection via binector inputs.
Description: Sets the signal source for control word 1 bit 0 (ON/OFF1).
Dependency: Refer to: p1055, p1056
Notice: For BI: p0840 = 0 signal, the motor can be moved, jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that originally powered up can also power down again.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: For drives with closed-loop speed control (p1300 = 20), the following applies:
- Bit 0 = 0: OFF1 (braking with the ramp-function generator, then pulse suppression and switching on inhibited)
For drives with closed-loop torque control (p1300 = 22), the following applies:
- Bit 0 = 0: Immediate pulse suppression
For drives with closed-loop torque control (activated using p1501), the following applies:
- Bit 0 = 0: No dedicated braking response, but pulse suppression when standstill is detected (p1226, p1227)
For drives with closed-loop speed/torque control, the following applies:
- Bit 0 = 0/1: ON (pulses can be enabled)
Description: Sets the signal source for control word 1 bit 0 (ON/OFF1).
Dependency: Refer to: p1055, p1056
Notice: For BI: p0840 = 0 signal, the motor can be moved, jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that originally powered up can also power down again.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: For drives with closed-loop speed control (p1300 = 20), the following applies:
- Bit 0 = 0: OFF1 (braking with the ramp-function generator, then pulse suppression and switching on inhibited)
For drives with closed-loop torque control (p1300 = 22), the following applies:
- Bit 0 = 0: Immediate pulse suppression
For drives with closed-loop torque control (activated using p1501), the following applies:
- Bit 0 = 0: No dedicated braking response, but pulse suppression when standstill is detected (p1226, p1227)
For drives with closed-loop speed/torque control, the following applies:
- Bit 0 = 0/1: ON (pulses can be enabled)
r0837.0...1 CO/BO: Drive Data Set DDS selected / DDS selected
Access level: 3 Calculated: - Data type: Unsigned8
Unit: - Scaling: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DDS select. bit 0 On Off -
01 DDS select. bit 1 On Off -
p0840[0...n] BI: ON/OFF1 / ON/OFF1
CU230P-2 CAN
CU230P-2 HVAC
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 722.0
p0840[0...n] BI: ON/OFF1 / ON/OFF1
CU230P-2 DP Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 2090.0

Table of Contents

Related product manuals