Siemens CU230P-2 DP - p31020 Multi-zone control interconnection; Zone_ctrl intercon; p31021 Multi-zone control configuration; Zone_ctrl config

Siemens CU230P-2 DP
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-406
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Setting for interconnecting multi-zone control
Value: 0: Removing the multi-zone control interconnection
1: Interconnecting multi-zone control
Notice: When multi-zone control is interconnected, outputs r31024 and r31027 are always connected to index 0 of parame-
ters p2253 and p2264. Any changes made to the command data set (CDS) in p2253 and p2264 are ignored.
Note: Re p31020 = 0:
The following BICO interconnections are automatically removed:
- p31023[0] = 0
- p31023[2] = 0
- p31026[0] = 0
- p31026[1] = 0
- p2253[0] = 0
- p2264[0] = 0
Re p31020 = 1:
The following BICO interconnections are automatically established:
- p31023[0] = r0755[0]
- p31023[2] = r0755[1]
- p31026[0] = r0755[2]
- p31026[1] = r0755[3]
- p2253[0] = r31024
- p2264[0] = r31027
Description: Sets the configuration for multi-zone control.
Value: 0: Setpoint 1 / multiple actual values
1: Two zones / highest value setting
2: Two zones / lowest value setting
Note: Re p31021 = 0:
The setpoint 1 and the output of the actual value processing are forwarded to the technology controller.
Re p31021 = 1:
The highest value setting ensures that the actual values of the two zones remain below their respective setpoint.
Re p31021 = 2:
The lowest value setting ensures that the actual values of the two zones remain above their respective setpoint.
p31020 Multi-zone control interconnection / Zone_ctrl intercon
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Min Max Factory setting
0 1 0
p31021 Multi-zone control configuration / Zone_ctrl config
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Min Max Factory setting
0 2 2