Siemens CU230P-2 DP - p20362 MFP 3 run-time group; MFP 3 RTG; p20363 MFP 3 run sequence; MFP 3 RunSeq; p20372 CI: PLI 0 input X; PLI 0 input X; r20373 CO: PLI 0 output Y; PLI 0 output Y

Siemens CU230P-2 DP
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-401
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Setting parameter for the run-time group in which the instance MFP 3 of the pulse generator is to be called.
Value: 5: Run-time group 5
6: Run-time group 6
9999: Do not calculate
Description: Setting parameter for the run sequence of instance MFP 3 within the run-time group set in p20362.
Note: The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description: Sets the signal source for input X of the polyline (20 breakpoints) of instance PLI 0.
Description: Display parameter for the output quantity Y of the polyline (20 breakpoints) of instance PLI 0
p20362 MFP 3 run-time group / MFP 3 RTG
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Min Max Factory setting
5 9999 9999
p20363 MFP 3 run sequence / MFP 3 RunSeq
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Data set: -
Min Max Factory setting
0 32000 960
p20372 CI: PLI 0 input X / PLI 0 input X
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Data set: -
Min Max Factory setting
- - 0
r20373 CO: PLI 0 output Y / PLI 0 output Y
Access level: 3 Calculated: - Data type: FloatingPoint32
Unit: - Scaling: PERCENT Data set: -